Diagram of SANTEK UPS power failure lamp
Release time: 2020-04-07 14:33:22 hits: 339
Fault phenomenon
Cause of failure
Investigation and solution
Short battery discharge time Battery aging Replace the battery in time
UPS overload Check load levels and remove unimportant loads
1# Fault indicator lamp and 6# The light is on and the buzzer is ringing UPS Shut down due to internal overheating ensure UPS It is not overloaded, the vent is not blocked, and the indoor temperature is not too high. wait for ten Minutes let go UPS Cool down and restart. If it fails, please contact the manufacturer
1# Fault indicator lamp and 5# The light is on and the buzzer is ringing UPS or UPS Shut down due to internal fault Output short circuit turn off UPS Remove all loads and confirm that there is no fault or internal short circuit in the load. Restart the machine. If it fails, please contact the manufacturer
1# Fault indicator lamp and 4# The light is on, UPS yowl UPS Shut down due to internal fault Please contact the manufacturer
1# Fault indicator lamp and 3# The light is on, UPS yowl UPS Overcharge protection action UPS Charger failure, please contact the manufacturer
The mains light flashes Mains voltage or frequency exceeds UPS Input range (at power on UPS Two calls in a second, eight in a row) here UPS Working in battery mode, save data and close the application to ensure that the utility is in UPS Allowable input voltage or frequency range
The zero and live lines of the city power supply are connected reversely, UPS One call in two minutes Reconnection to make the zero fire line of the utility power connect correctly
1# Fault indicator lamp and 2# The light is on, UPS yowl Battery mode UPS Or load equipment failure overload Check load levels and remove non critical equipment, recalculate load power and reduce connections to UPS Check whether the load equipment is faulty
The battery light is flashing The battery voltage is too low or the battery is not connected inspect UPS Battery part, connect the battery, if the battery is damaged, quickly replace the battery
1# The fault light is on, the battery light is flashing, and the buzzer sounds once a second UPS Partial failure charge Please contact the manufacturer
The power supply is normal, UPS No access to electricity UPS Input circuit breaker open circuit Reset the circuit breaker manually
Short battery discharge time The battery is under charged keep UPS Connect the mains power for more than three hours to recharge the battery
UPS overload Check load level and remove non critical equipment
Battery aging, capacity reduction To replace the battery, please contact your dealer to obtain the battery and its components
After pressing the power on key, UPS Unable to start Press the power button for a short time Press the power on key for more than one second to start UPS
UPS The battery is not connected or the battery voltage is low and it is started with load Connect well UPS Battery, if the battery voltage is low, turn off the power first and then turn it on
UPS Internal failure Please contact the manufacturer